Impulse 2123 Bedienungsanleitung Seite 10

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 25
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 9
Interface Biasing
1K-ohm pull up/pull down combination resistors bias the receiver inputs and are
handled automatically for each mode. The pull-up (PU) and pull-down (PD) resistor
settings are shown in the table below.
Mode PU Setting PD Setting
RS-232
Always Off Always Off
RS-422
Always Off Always Off
RS-485
Always On Always On
Line Termination
A 120-ohm resistor is across the RS-422/485 input. If multiple devices are
configured in an RS-485 network, only the devices on each end should have the
termination in place.
Termination configuration is software selectable for both full- and half-duplex RS-
485. By default, line termination is disabled, and this configuration can be set by
placing a check next to ‘Enable Termination’ in the ‘RS-485 Advanced
Configuration’ field, as shown in the image below.
© Sealevel Systems, Inc.
- 8 -
SeaLINK.SC User Manual
Seitenansicht 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 24 25

Kommentare zu diesen Handbüchern

Keine Kommentare