Visit our website www.dataforth.com
175
Industrial Loop Isolators and Transmitters
DSCL
DSCL24
(
Multi-Channel
)
Factory Configurable Isolator - DIN or Panel Mount
Features
Uses Universal Power Supply of 24 to 60V or
85 to 230V AC/DC
Factory Configured Soldered Jumpers Allows
up to 250+ I/O Settings
One Input to Two Output Splitter Simplifies a
Common Requirement
Three-Way Isolation for 2300Vrms Protection
Prevents Ground-Loop Problems
Prevents the Transfer of Interference
Voltages and Currents
High Accuracy Over Full Span
No Recalibration or Maintenance Required
Narrow DIN Package, Mounts up to 27
Devices into a 19 Rack Space
DIN Rail or Panel Mountable
CE Compliant
Figure 1: DSCL24 Block Diagram
Description
Each multi-channel DSCL24 module provides up to 252 different configurations
of process current or voltage inputs and outputs. The factory default setting
provides 4-20mA input and output current. Alternatively, users may complete
and submit a specific configuration table that instructs the factory on how to solder
in configuration jumpers.
Each module provides full 3-way isolation with 2300Vrms CMV input to output
and 3700Vrms CMV power supply to I/O protection. Two module versions are
offered that accept universal power supply of either 24 to 60VDC or AC and
85 to 230VDC or AC with the alternating current usage accepting 45 to 400Hz
power.
Seitenansicht 0
1 2 3

Inhaltsverzeichnis

Seite 1 - Multi-Channel

DSCLVisit our website www.dataforth.com175Industrial Loop Isolators and TransmittersDSCLDSCL24 (Multi-Channel)Factory Configurable Isolator - DIN or P

Seite 2 - Factory Configuration

Industrial Loop Isolators and TransmittersDSCLFor information call 800-444-7644176SpecificationsInput Range(1)4-20mAInput Limit 40mA, ±40mA(Iin); 40V,

Seite 3 - Dimensions and Mounting

DSCLVisit our website www.dataforth.com177Industrial Loop Isolators and TransmittersDSCLOrdering InformationModel Input (default*) Out

Kommentare zu diesen Handbüchern

Keine Kommentare